Figure 1.17 Equivalent circuit for the computation of body currents in the presence of an EXCP.
Example 1.1 A hemispherical electrode of radius r0 = 2 m is buried in the ground of resistivity ρ = 200 Ω m and connected to a tower crane (Figure 1.13). A person is standing 10 m away from the center of the hemisphere and holding a metal hook electrically connected to the hemisphere. A ground-fault causes a current i = 100 A to flow into the earth through the hemisphere. Determine the electric current iB through the person’s body in the case of touch, assuming a conventional body resistance of 1 kΩ.
Solution
From Eq. 1.9, the ground potential rise of the hemisphere is:
The touch voltage is V(r0)–V(r), where V(r) can be calculated with Eq. 1.8 with r = 10 m.
Vt = V (r0 ) − V (r)= 1114.6 V
From Eq. 1.16, the body current with RB = 1 kΩ, and RBG = 1.5ρ = 300 Ω, is:
1.10 Identification of Extraneous-Conductive-Parts
With the purpose of reducing touch voltages, applicable standards require that in each installation main protective bonding conductors connect to the main ground busbar the EXCPs, which may include: metal installation pipes for gas, water, heating, etc.; non-insulating floors and walls; exposed metallic structural parts of the building. These items are mere examples of conductive parts that may require the protective equipotential bonding; the identification of EXCPs is crucial for safety and a verification if conductive parts are EXCPs is necessary before connecting them to the ground busbar.
BS 76718 defines an EXCP as “a conductive part liable to introduce a potential, generally earth potential, and not forming part of the electrical installation.”
The term earth potential is generally assumed to be zero volts and introduced by the general mass of the earth into the installation. This definition implies that such conductive parts would originate outside the building and be in contact with the ground. If this can be verified by visual inspection, the part in question should be bonded as close as practicable to their point of entry within the building. It is important to clarify that for bonding purposes, the point of connection of pipework should take place along the section of the pipe from the meter into the building, which is owned by the user, and not on the section that comes in from the road into the meter. This prevents corrosion issues to the service pipework.
If it is not possible to verify by visual inspection alone that a conductive part is an EXCP, a measurement of the resistance REX between the conductive part in question and the main ground busbar should be performed. If the measured resistance REX satisfies Eq. 1.18, based on the circuit of Figure 1.16, the conductive part in question is not to be considered an EXCP.
Vth is the nominal voltage to ground of the installation (in V); RB is the standard value of body resistance of 1 kΩ; IBM (A) is the maximum value of body current that is deemed acceptable to the designer. Threshold values for IBM may be 0.5 mA (i.e., the threshold of perception), 10 mA (the threshold of let-go), or 30 mA.
However, the designer should assess if the measured resistance to the ground of the concerned conductive part may change (i.e., decrease) throughout the lifetime of the installation.
If, for example, the chosen threshold of safe current is 30 mA with vth = 230 V, and the measured resistance between a conductive part not forming part of the electrical installation (a presumed EXCP) and the ground is greater than 6.67 kΩ, then no connection to the main ground terminal of the metal part in question would be required.
It is important to recognize that the indiscriminate connection to the ground terminal of mere conductive parts that are not EXCPs may cause fault potentials to be transferred throughout the installation. This can cause the risk of electric shock for persons standing outside of the installation that is in contact with the presumed EXCP that has become live (e.g., a metallic fence).
1.11 Measuring Touch Voltages
Measurements after construction of the installation can verify the adequacy of the electrical design of the substation [30]. Measuring touch voltages [31–33] includes two choices: measure the prospective touch and step voltages, by using a high-impedance voltmeter, or measure the effective touch and step voltages occurring across an appropriate resistance of 1 kΩ, which represents the human body.
For touch voltage measurements a current injection method may be used (Figure 1.18).
Figure 1.18 Touch voltage measurement with the current injection method.
An alternating voltage of approximately the system frequency is applied between the facility ground electrode and an auxiliary ground electrode, located far enough to guarantee separate zones of influence (e.g., 4 or 5 times the maximum dimension of the facility ground electrode). A test current im is injected into the facility grounding system, which causes a measurable ground potential rise.
The test current should be so high that the measured touch voltage, referred to as the test current, is greater than possible disturbance voltages; according to EN 50522, this may be ensured for test currents of at least 50 A. Always according to EN 50522, the measuring electrodes for the simulation of the feet, connected in parallel, must have a total area of 400 cm2, lie on the ground with a minimum total force of 500 N, and placed at a distance of 1 m from the equipment of the installation, or from an EXCP. During the test, the auxiliary ground electrode may assume a dangerous ground potential rise, and therefore should be guarded.