Introduction To Modern Planar Transmission Lines. Anand K. Verma

Чтение книги онлайн.

Читать онлайн книгу Introduction To Modern Planar Transmission Lines - Anand K. Verma страница 40

Introduction To Modern Planar Transmission Lines - Anand K. Verma

Скачать книгу

wave” from load to the source, whereas the wave incident at the load V+e(ωt − γx) appears as the “backward‐traveling” wave. The voltage drop across the load is

      (2.1.83)equation

      Keeping in view that the origin of the distance (x = 0) is at the load, the line voltage and current at the load end are written, from equation (2.1.79), as follows:

      (2.1.84)equation

      The voltage reflection coefficient at the load end is defined as follows:

      (2.1.85)equation

      The expression to compute the reflection coefficient at the load end is obtained from the above equations (2.1.83) – (2.1.85): equations:

      The mismatch of a load impedance ZL with the characteristic impedance Z0 of a line is the cause of the reflection at the load end. For the condition ZL = Z0, the matched load terminated line avoids the reflection on a line, as ΓL = 0. At any distance x, the reflection coefficient is a complex quantity with both the magnitude and phase expressed as follows:

      (2.1.87)equation

      For a lossless transmission line, the above equations are written as follows:

      In the above equations, the origin is at the load end, i.e. x < 0. The maxima and minima of the voltage and current waves along the line occur due to the phase variation along the line. The voltage maximum occurs at ej(ϕ + 2βx) = + 1. In this case, both the forward and reflected waves are in‐phase. The voltage minimum occurs at ej(ϕ + 2βx) = − 1. In this case, both the forward and reflected waves are out of phase. Finally, the maxima and minima of the voltage on a line are given as follows:

      (2.1.90)equation

      The reflection coefficient Γ(x) at any location x from the load end is related to the reflection coefficient at the load ΓL by

      (2.1.91)equation

      The measurable quantity voltage standing wave ratio (VSWR) is defined as follows:

      (2.1.92)equation

      For a lossless line, the VSWR is constant along the length of a line. Likewise, the current standing wave ratio is also defined.

      The amplitude factor V+ is determined by the reflections at both the source and load ends.

      Figure (2.8b) shows that the port voltage images and the line current images, at the input port – aa, are related to the source voltage images and its internal impedance Zg by

      (2.1.95)equation

      However, the reflection coefficient at the source end is

      Therefore, the amplitude of the voltage wave launched by the source is

      2.1.8 Application of Thevenin's Theorem to Transmission Line

Скачать книгу