is produced in the airgap of the machine.

      The importance of a three‐phase system creating a constant field cannot be stressed enough. The constant magnitude flux allows power, megawatts, to be transformed inside an electric machine from electrical to mechanical power, and vice versa. It is important to remember that a constant‐magnitude flux produces a constant‐magnitude torque.

      1.7.1 Magnetic Representation

      To describe the fundamental principles describing the operation of a synchronous machine, it is convenient to use the constructs of an ideal salient pole rotor machine connected to an infinite bus. The infinite bus represents a bus which can deliver or absorb active and reactive power without any limitations and whose voltage and frequency are essentially constant. The ideal machine has zero resistance and leakage reactance, infinite permeability, and no saturation, as well as zero reluctance torque.

Schematic illustration of the production of stator rotating field.

      Source: Courtesy of Voith.

      The production of torque in the synchronous machine results from the natural tendency of two magnetic fields to align themselves. The magnetic field produced by the stationary armature is denoted as Φs. The magnetic field produced by the rotating field is Φf. The resultant magnetic field is

equation

      The flux, Φr, is established in the airgap of the machine. (Bold symbols indicate vector quantities.)

Schematic illustration of phasor diagram of an unsaturated salient pole generator.

      Due to saliency, the reactance measured at the terminals of the generator is a function of rotor positon and thus the two reactance theory can be applied [1]. The armature current Ia can be resolved into two components, namely, Id and Iq representing direct and quadrature axis currents. Id is in time quadrature with the internal excitation voltage Ef, where Iq is in time phase with Ef. The direct axis component of the armature Id produces an armature reaction flux Φad along the axis of the field poles. Iq however produces an armature reaction flux Φaq in space quadrature with the field poles. The magnetic effect of Φad is centered on the axis of the field pole where the magnetic effect of Φaq is centered on the inter polar axis. The armature reaction flux Φs is the space phasor sum of the components Φad and Φaq. It follows that the resultant flux Φr is a result of the space phasor sum of the main field flux Φf and armature reaction flux Φs.

      1.7.2 Generator Mode: Steady State Using Vectors

      This section describes various practical use diagrams of a salient pole machine that is operating under steady‐state conditions [2].

Schematic illustration of the vector diagram of generator with a lagging power factor. Schematic illustration of the vector diagram of generator with a leading power factor.

      Referring to Figure 1.7-4, there are some key differences worth noting while operating at a leading power factor. The armature current I is now leading the terminal voltage Et by the angle φ. The quadrature axis components Iq and IqXq