Handbook of Microwave Component Measurements. Joel P. Dunsmore

Чтение книги онлайн.

Читать онлайн книгу Handbook of Microwave Component Measurements - Joel P. Dunsmore страница 24

Handbook of Microwave Component Measurements - Joel P. Dunsmore

Скачать книгу

      (1.28)equation

      or in the case of a 2‐port network terminated by an arbitrary load then

      (1.29)equation

      Similarly, the output impedance of a network that is sourced from an arbitrary source impedance is

      Another common term for the input impedance is the voltage standing wave ratio, called VSWR (also simply called SWR), and it represents the ratio of maximum voltage to minimum voltage that one would measure along a Z0 transmission line terminated in some arbitrary load impedance. It can be shown that this ratio can be defined in terms of the S‐parameters of the network as

      (1.31)equation

      (1.32)equation

      It's also common to write

      (1.33)equation

      Another term related to the input impedance is return loss, which is alternatively defined as

      (1.34)equation

      with the second definition being most properly correct, as loss is defined to be positive in the case where a reflected signal is smaller than the incident signal. But, in many cases, the former definition is more commonly used; the microwave engineer must simply refer to the context of the use to determine the proper meaning of the sign. Thus, an antenna with 14 dB return loss would be understood to have a reflection coefficient of 0.2, and the value displayed on a measurement instrument might read −14 dB.

      For transmission measurements, the figure of merit is often gain or insertion loss (sometimes called isolation when the loss is very high). Typically this is expressed in dB, and similarly to return loss, it is often referred to as a positive number. Thus

      Insertion loss or isolation is defined as

      (1.36)equation

      Notice that in the return loss, gain, and insertion loss equations, the dB value is given by the formula 20log10(|Snm|), and this is often a source of confusion because common engineering use of dB has the computation as XdB = 10log10(X). This apparent inconsistency comes from the desire to have power gain when expressed in dB be equal to voltage gain, also expressed in dB. In a device sourced from a Z0 source and terminated in a Z0 load, the power gain is defined as the power delivered to the load relative to the power delivered from the source, and the gain is

      The power from the source is the incident power |a1|2, and the power delivered to the load is |b2|2. The S‐parameter gain is S21 and in a matched source and load situation is simply

      (1.38)equation

      (1.39)equation

      A few more comments on power are appropriate, as power has several common meanings that can be confused if not used carefully. For any given source, as shown in Figure 1.1, there exists a load for which the maximum power of the source may be delivered to that load. This maximum power occurs when the impedance of the load is equal to the conjugate of the impedance of the source, and the maximum power delivered is

      (1.41)equation

      If one considers a passive two‐port network and conservation of energy, power delivered to the load must be less than or equal to the power incident on the network minus the power reflected, or in terms of S‐parameters

      (1.42)equation

      which leads the well‐known formula for a lossless network

      (1.43)equation

       1.3.2 Phase Response of Networks

      While most of the discussion thus far about S‐parameters refers to powers, including incident, reflected, and delivered to the load, the S‐parameters are truly complex numbers and contain both a magnitude and phase component. For reflection measurements, the phase component is critically important and provides insight into the input elements of the network. These will be discussed in great detail as part of

Скачать книгу