Arc Flash Hazard Analysis and Mitigation. J. C. Das

Чтение книги онлайн.

Читать онлайн книгу Arc Flash Hazard Analysis and Mitigation - J. C. Das страница 25

Arc Flash Hazard Analysis and Mitigation - J. C. Das

Скачать книгу

PPE, or the maximum HRC for that type of equipment. Also, arc flash boundary needs to be specified.

      A maximum duration of 2 seconds for the total fault clearance time of an arc flash event is considered, though, in some cases, the fault clearance time can be higher. In IEEE 1584 Guide Annexure B, it is stated that: “if the time is longer than 2 seconds, consider how long a person is likely to remain in the location of the arc-flash. It is likely that a person exposed to arc flash will move away quickly, if it is physically possible and 2 seconds is a reasonable maximum time for calculations. A person in a bucket truck or a person who has crawled into equipment may need more time to move away.”

      For a 30-kA, 2-second fault in 13.8-kV switchgear, the incident energy boundary is 3539 in equal to 295 ft. For 1-second fault duration, it is 144.6 ft. The arc flash boundary at which a worker can be exposed to 1.2 cal/cm2 of incident energy and sustain threshold of second degree burns seems to be very large.

Arc Duration in Seconds Arc Flash Boundary in Inches Incident Energy, cal/cm
0.050 36 3.8
0.5 147 38
1.0 225 75
1.5 288 113
2 343 151
Accident Occurrence Percentage
When the operator or worker is working with equipment doors open 65
When the operator happens to be in front of a closed door and the equipment is not arc resistant 10
When the operator is not present at all, and the equipment is not arc resistant 25

      1.11.1 Arc Flash Hazard with Equipment Doors Closed

      There is some controversy in interpreting the intent of NFPA 70E, whether the arc flash hazard exists at all times, with the equipment door closed, or it exists only when the doors of an energized equipment are opened for maintenance? Let us first consider most common reasons for arc flash accidents:

       human error

       mechanical faults

       failed connections, loose connections, and terminals

       Adverse ambient conditions and pollution. This should consider pollution specific to plant operation, that is, corrosive gases and vapors may be present.

       rodents.

      It is the collective experience of the Technical Committee on Electrical Safety in the Workplaces that normal operation of the enclosed electrical equipment, operating at 600V or less, that has been properly installed and maintained by qualified persons is not likely to expose the employee to an electrical hazard.

      It is also the opinion of the committee that there is little risk in performing normal operations of electrical equipment and devices, such as opening and closing circuit breakers, motor control centers (MCCs), or starters. When the committee states “interacting with equipment in a manner that could cause an arc flash hazard,” it refers to operations, such as racking circuit breakers or installing and removing MCC buckets.

      The internal arcing fault can be caused by various factors, such as:

      1 Insulation defects due to quality deterioration of components

      2 Overvoltages of atmospheric origin or generated within the equipment due to switching transients

      3 Incorrect operation due to not adhering to the procedures

      4 Inadequate training of the persons involved with installation, maintenance, and operation

      5 Breakage or tempering of safety interlocks

      6 Highly polluted atmospheric conditions, high humidity, temperatures, corrosive gases, and salt-laden winds

      7 Overheating of the contact area due to presence of corrosive agents, loose connections.

      8 Faulty assemblies

      9 Lack of proper protection and inadequate relaying. Though protective relaying by itself will not prevent an arcing fault, it will limit the arc fault energy and consequently equipment damage.

      10 Insufficient maintenance and testing procedures, like insulation resistance records, infrared testing, and partial discharge measurements which can indicate a deteriorating insulation situation.

Скачать книгу