Arc Flash Hazard Analysis and Mitigation. J. C. Das

Чтение книги онлайн.

Читать онлайн книгу Arc Flash Hazard Analysis and Mitigation - J. C. Das страница 21

Arc Flash Hazard Analysis and Mitigation - J. C. Das

Скачать книгу

240 V or less.

       The circuit is supplied by one transformer.

       The transformer supplying the circuit is rated less than 125 kVA.

      This qualification has now been removed in 1584, 2018 edition.

      The user is referred to IEEE Guide 1584 for three-phase systems rated less than 240 V.

      Ralph Lee equations from Reference [11] are as follows:

      Maximum power in a three-phase arc is:

      (1.5)

      where MVAbf is bolted fault mega-volt-ampere (MVA).

      The distance in feet of a person from an arc source for a just curable burn, that is, skin temperature remains less than 80°C, is:

      where t is the time of exposure in seconds.

      The equation for the incident energy produced by a three-phase arc in open air on systems rated above 600 V is given by:

      where:

       D = distance from the arc source in inches

       F = bolted fault short-circuit current, kA

       V = system phase-to-phase voltage, kV

       tA = arc duration in seconds.

      For the low voltage systems of 600 V or below and for an arc in the open air, the estimated incident energy is:

      (1.8)

      where EMA is the maximum open air incident energy in cal/cm2, F is short-circuit current in kA, range 16–50 kA, and DA is distance from arc electrodes, in inches (for distances 18 in and greater).

      The estimated energy for an arc in a cubic box of 20 in, open on one side is given by:

      where EMB is the incident energy and DB is the distance from arc electrodes, inches (for distances 18 in and greater).

      1.8.2 IEEE 1584 Guide Equations

      This is based on IEEE 2002 Guide. Included here for reference and completeness.

      Source: IEEE 1584-2018 Guide [9]. © 2002 IEEE. Also see Chapter 3.

Classes of Equipment Enclosure Size (in) Typical Bus Gaps (mm)
15-kV switchgear 45×30×30 152
15-kV MCC 36×36×36 152
5-kV switchgear 36×36×36 104
5-kV switchgear 45×30×30 104
5-kV MCC 26×26×26 104
Low voltage switchgear 20×20×20 32
Shallow low voltage MCCs and panel boards 14×12×≤8 25
Deep voltage MCCs and panel boards 14×12×>8 25
Cable junction box 14×12×≤8 or14×12×>8 13

      (1.10)

      where:

       Ia = arcing current in kA

       G = conductor gap in mm, typical conductor gaps are specified in [9] (see Table 1.5)

       K = −0.153 for open air arcs, −0.097 for arc in a box

       V = system voltage in kV

       Ibf = bolted three-phase fault current kA, rms symmetrical.

      For systems of 1 kV and higher, the following equation is solved:

      This expression is valid for arcs both in open air and in a box. Use 0.85 Ia to find a second arc duration. This second arc duration accounts for variations in the arcing current and the time for the overcurrent device to open. Calculate incident energy using both 0.85 Ia and Ia and use the higher value.

      Incident energy at working distance, an empirically derived equation,

Скачать книгу