Arc Flash Hazard Analysis and Mitigation. J. C. Das

Чтение книги онлайн.

Читать онлайн книгу Arc Flash Hazard Analysis and Mitigation - J. C. Das страница 22

Arc Flash Hazard Analysis and Mitigation - J. C. Das

Скачать книгу

target="_blank" rel="nofollow" href="#ulink_10f3d229-9c7b-54f9-ac51-996c5fde305b">(1.12)

       En = Incident energy (J/cm2) normalized for time and distance

       K1 = −0.792 for open air and −0.555 for arcs in a box

       K2 = 0 for ungrounded and high resistance grounded systems and −0.113 for grounded systems. Low resistance grounded, high resistance grounded, and ungrounded systems are all considered ungrounded for the purpose of calculation of incident energy.

       G = conductor gap in mm (Table 1.5).

      Conversion from normalized values gives the equation:

      where:

       E = incident energy in J/cm2

       Cf = calculation factor = 1.0 for voltages above 1 kV and 1.5 for voltages at or below 1 kV

       t = arcing time in seconds

       D = distance from the arc to the person, working distance (Table 1.6)

       x = distance exponent as given in Reference [9] and reproduced in Table 1.7.

      A theoretically derived equation can be applied for voltages above 15 kV or when the gap is outside the range in Table 1.5 (from Reference [9]).

      (1.14)

      Source: IEEE 1584-2018 Guide [9]. © 2002 IEEE. Also see Chapter 3.

Classes of Equipment Working Distance
15-kV switchgear 36
15-kV MCC 36
5-kV switchgear 36
5-kV switchgear 36
5-kV MCC 36
Low voltage switchgear 24
Shallow low voltage MCCs and panel boards 18
Deep voltage MCCs and panel boards 18
Cable junction box 18

      Source: IEEE 1584 Guide [9]. © 2002 IEEE.

System Voltage, kV Equipment Type Typical Gap between Conductors Distance × Factor
0.208–1 Open air 10–40 2.000
Switchgear 32 1.473
MCC and panels 25 1.641
Cable 13 2.000
>1–5 Open air 102 2.000
Switchgear 13–102 0.973
Cable 13 2.000
>5–15 Open air 153 2.000
Switchgear 13–153 0.973
Cable 13 2.000

      For the arc flash protection boundary, defined further, the empirically derived equation is:

      where EB is the incident energy in J/cm2 at the distance of arc flash protection boundary.

      For Lee’s method:

      (1.16)

      Due to complexity of IEEE equations, the arc flash analysis is conducted on digital computers. It is obvious that the incident energy release and the consequent hazard depend upon:

       The available three-phase rms symmetrical short-circuit currents in the system. The actual bolted three-phase symmetrical fault current should be available at the point where the arc flash hazard is to be calculated. In low voltage systems, the arc flash current will be 50–60% of the bolted three-phase current, due to arc voltage drop. In medium and high voltage systems, it will be only slightly lower than the bolted three-phase current. The short-circuit currents are accompanied by a DC component, whether it is the short circuit of a generator, a motor, or a utility source. However, for arc flash hazard calculations, the DC component is ignored. Also, any unsymmetrical fault currents, such as line-to-ground fault currents, need not be calculated. As evident from the cited equations, only

Скачать книгу