Arc Flash Hazard Analysis and Mitigation. J. C. Das

Чтение книги онлайн.

Читать онлайн книгу Arc Flash Hazard Analysis and Mitigation - J. C. Das страница 19

Arc Flash Hazard Analysis and Mitigation - J. C. Das

Скачать книгу

1.7 shows a comparison of Equation (1.4) and Z-shaped body current time developed by Biegelmeier.

      1.6.1 Resistance of Human Body

      For DC and AC 50 or 60 HZ currents, the human body can be approximated by a resistance. For the calculation of this resistance, the current path is considered from:

       one hand to both feet

       from one foot to another foot.

      NFPA 70E states that energized parts operating at less than 50 volts are not required to be de-energized to satisfy an “electrical safe working condition.” It further lays down that considerations should be given to the capacity of the source, any overcurrent protection between the source and the worker, and whether the work task related to the source operating at less than 50 volts increases exposure to electrical burns or to explosion from an electric arc.

      Reference [29] contends that 50 V is inadequate and calculates the maximum and minimum body resistance for path from arm-to-arm and arm-to-leg of the order of 300–500 Ω. IEC standard 604791 [23] recommends shock voltages of less than 50 V in some situations. Some jurisdictions, for example, in France, the safe voltage limit is accepted as 35–50 V. However, NFPA 70E qualifies the 50 V limits by additional cautionary statements as indicated above.

      Source: Reference [23].

Material Resistance in MΩ
Rubber gloves or soles >20 0
Dry concrete above grade 1 0–5.0
Dry concrete on grade 0.2–1 0
Leather sole, dry, including foot 0.1–0.5
Leather sole, damp, including foot 0.05–0.2
Wet concrete 0.01–0.05

      Source: Reference [23].

      See also Section 2.4.

      NFPA and National Fire Incident Reporting Systems (NFIRS) statistics of fire hazard can be viewed on websites. These statistics are based upon:

       heat source, that is, arcing

       contributing factors like electrical failure or malfunction

       equipment involved in electrical distribution, lighting, and power transfer.

      Source: Reference [23].

Zone Boundaries Physiological Effects
AC-1 Up to 0.5 mA, curve a Perception possible but usually no “startled” reaction
AC-2 0.5 mA up to curve b Perception and involuntary muscular contractions likely but usually no harmful physiological effects
AC-3 Curve b and above Strong involuntary muscular contractions, difficulty in breathing. Reversible disturbances of heart function. Immobilization may occur. Effects increasing with current magnitude. Usually no organic damage to be expected.
AC-4a Above curve c1 Pathophysiological effects may occur, such as cardiac arrest, burns, or other cellular damage. Probability of ventricular fibrillation increasing with current magnitude and time
c1–c2 AC-4.1: Probability of ventricular fibrillation increasing up to about 5%
c2–c3 AC-4.2: Probability of ventricular fibrillation increasing up to about 50%
Beyond curve c3 AC-4.3:

Скачать книгу